Marine Cables
MariTox Marine Flame Retardant Medium Voltage Cables MariTox Marine Flame Retardant Power & Control Cables MariFlex Marine Fire Resistant Power & Control Cables other

Power Distribution Cables  

2-4 conductors Type E, X distribution cables


Construction

Conductor:

Stranded copper conductor tin or alloy coated where necessary for the application , conductor per ASTM or IEC

60228.

Separator tape: optional

Insulation:

Ethylene propylene rubber(EPR), or cross-linked polyethylene(XLPE) according to IEEE 1580 2010 Type E,

X,Type T, T/N, S, P, LSX and LSE as option.

Filler: Conductors cabled with fillers, where necessary, to form a round foundation

Grounding conductor: optional

Binder tape: optional

Shielding: optional

Jacket: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N,

Type T, CP, CPE, L, P or TPO jacket as option (optional for Type P with HD thicknesses).

Armor: optional and shall be nonmagnetic

Sheath: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N,

Type T, CP, CPE, L, P or TPO sheath as option (optional except for tinned copper braid armoured cables).

Optional: For halogen-free constructions, Type LSX, LSE or LSS insulation shall be used with a Type L or TPO

jacket/sheath. 

Table B.2—Typical dimensions and weights; single-, two-, three-, and four-conductor 2000 V; Type E and X distribution cables

Number of conductors AWG /kcmil Unarmored Armored Armored and sheathed
Nom. dia. (in) Approx. weight (lb/1000 ft) Nom. dia. (in) Approx. weight (lb/1000 ft) Nom. dia. (in) Approx. weight (lb/1000 ft)
2 14 0.42 82 0.48 106 0.61 174
2 12 0.46 108 0.52 135 0.65 209
2 10 0.55 162 0.61 191 0.74 276
2 8 0.65 229 0.71 262 0.88 392
2 6 0.71 326 0.77 363 0.94 503
2 4 0.81 453 0.87 496 1.04 652
2 2 0.97 702 1.03 752 1.2 935
2 1 1.09 864 1.15 920 1.32 1123
2 1/0 1.17 1041 1.23 1103 1.4 1318
2 2/0 1.27 1249 1.33 1317 1.5 1549
2 3/0 1.37 1512 1.43 1586 1.6 1834
2 4/0 1.49 1844 1.55 1922 1.79 2308
2 250 1.63 2182 1.69 2268 1.93 2687
2 300 1.8 2688 1.86 2782 2.09 3220
2 350 1.9 3062 1.96 3162 2.19 3622
2 400 2 3473 2.06 3579 2.29 4061
2 500 2.16 4227 2.22 4341 2.45 4859
2 600 2.38 5053 2.44 5167 2.67 5733
2 750 2.6 6146 2.66 6260 2.95 7044
3 12 0.49 141 0.55 168 0.68 245
3 10 0.59 211 0.65 242 0.77 324
3 8 0.69 303 0.75 338 0.92 475
3 4 0.91 648 0.97 695 1.14 868
3 2 1.04 933 1.1 986 1.27 1180
3 1 1.17 1168 1.23 1230 1.4 1445
3 1/0 1.25 1404 1.31 1469 1.48 1698
3 2/0 1.36 1714 1.42 1788 1.59 2035
3 4/0 1.6 2580 1.66 2663 1.89 3057
3 250 1.81 3146 1.87 3243 2.1 3683
3 300 1.92 3698 1.98 3801 2.21 4265
3 350 2.03 4252 2.09 4360 2.32 4849
3 400 2.14 4833 2.2 4947 2.43 5460
3 500 2.31 5890 2.37 6004 2.6 6555
3 600 2.55 7060 2.61 7174 2.9 7944
3 750 2.85 8847 2.91 8961 3.2 9815
4 14 0.49 131 0.55 158 0.67 228
4 10 0.64 261 0.7 294 0.83 390
4 8 0.76 381 0.82 421 0.99 569
4 4 1 831 1.06 881 1.22 1056
4 2 1.14 1205 1.2 1261 1.37 1472
4 1 1.29 1516 1.35 1584 1.52 1819
4 1/0 1.38 1840 1.44 1914 1.61 2164
4 2/0 1.51 2260 1.57 2340 1.8 2714
4 3/0 1.63 2762 1.69 2848 1.92 3248
4 4/0 1.83 3463 1.89 3560 2.13 4025
4 250 2 4091 2.06 4197 2.29 4679
4 300 2.12 4812 2.18 4926 2.42 5458
4 350 2.25 5562 2.31 5676 2.54 6214
4 400 2.37 6302 2.43 6416 2.66 6980
4 500 2.56 7729 2.62 7843 2.91 8616
4 600 2.89 9433 2.95 9547 3.24 10 412
4 750 3.16 11 587 3.22 11 701 3.51 12 642

 

NOTE—These values are for reference purposes only and should not be construed as requirements. Dimensions are based on the use of Class B conductors. Weights of armored constructions are based on aluminum braid armor. It is recommended that the user/specifier contact the manufacturer for manufacturer specific values.